Live Load Capacity Table
& Dimension Requirements
Traditional vs
CCC New Standard
Engineering Criteria
Installation Guide
Minimum clearance with 2 1/2” x1 1/4” Corrugated Roof decking; 9” max. width of joist top. Carriage Bolts must be Grade 5. Provided Grade 5 Bolts dyed yellow.

 
Tube Framing Clamp System
Allowable Load (pounds) vs. Span
a-h
Tube Size (inches) Load Type Span (feet)
3 4 5 6 7 8 9 10
HSS 4" x 2" x 1/8" concentrated 2,000 2,000 2,000 2,000 1,801 1,572 1,318 1,067
uniform 2,000 2,000 2,000 2,000 2,000 2,000 2,000 1,708
HSS 4" x 2" x 3/16" concentrated 2,000 2,000 2,000 2,000 2,000 2,000 1,820 1,474
uniform 2,000 2,000 2,000 2,000 2,000 2,000 2,000 2,000
Component Capacities Download
Positive
Uplift
Negative
Allowable Load (pounds)
Standard End Clamp 750 -
Joist Grip end Clamp 1,000 1,000
T-Bracket 1,000 1,000
InLine End Clamp 1,000 1,000
Girder Clamp 1,000 -
Cross Support Bracket 1,000 -
a) Allowable concentrated load at middle of span. Allowable
loads are net (weight of tube has been accounted for).
b) Multiple loads, that are symmetrically placed and whose
total equals the tabulated value, may be used.
c) The reaction to each clamp bracket must be limited to a net
value of the clamp's charted capacity.
d) Allowable loads have been limited to 2,000 lbs maximum.
e) Allowable loads are based on 46 ksi minimum yield steel
(A500, Gr. B), the AISC specification and a safety factor of 2.0.
f) Loads in bold (1,067) are governed by applied-load deflection
limit of Span / 240; (e.g., 0.50" for 10' span).
g) Tube's 4" dimension is vertical. Span is horizontal.
h) Tube weights: 4.75 lbs/ft for 1/8" wall, and 6.87 lbs/ft for 3/16"
wall. Weights and thicknesses are nominal.
 

NOTE: Modification or additional loading of any structure must be reviewed by a structural engineer. Each Chicago Clamp Systems® (CCS) application must be selected under direction and installed under supervision of a structural engineer. CCS does not increase load capacity of any structure. Chicago Clamp Company (CCC) takes no responsibility for the load capacity of any building. Only use components provided by CCC.