ANALYSIS
& TESTING OF TUBE SYSTEM FOR ROOF-LOAD TRANSFER TO JOISTS
Summary
Chicago Clamp Company’s
Tube Frame, for the transferring of roof loads
to joists, consists of steel components: End
Clamps, framing members (tubes), T-brackets,
and hardware. The End Clamps connect the primary
tubes to the top chords of the joists. The T-brackets
connect the secondary tubes to the primary tubes.
The positions of the secondary tubes between
joists can be adjusted by sliding the T-brackets.
Analysis of the End Clamp
indicates that it can support an allowable static
load (net load) of 750 lbs. The smallest maximum
load, applied in static testing, was 3,610 lbs
per clamp. The clamp’s static fracture
load was not reached. Analysis and testing included
consideration of both shear and bending of the
bolts that transfer load from the tubes to the
clamps. The bolts are SAE J429 (Grade 5), tightened
to a usual snug condition. Analysis and testing
were based on the worst-case position of support.
In that case, the center of the support is 5"
from the near edge of the clamp’s deep
section (i.e., the shallow section spans 5").
Analysis of the T-bracket
indicates an allowable static load of substantially
more than 750 lbs. A static test load of 4,910
lbs per bracket was applied with no failure.
The tested framing system
consisted of cold-formed HSS 4” x 2”
x 1/8” tubes (4" vertical, weighing
4.75 pounds per foot and conforming to A500
Grade B [46 ksi minimum yield]). The maximum
span tested was 10'. Analysis was based on the
2005 edition of the AISC Specification (13th
edition of the Steel Construction Manual) and
a minimum safety factor of 2.0, which exceeds
the minimum required value of 1.67 for flexure.
A static strength-based allowable of 1,572 lbs
was calculated for a concentrated load applied
at the middle of an 8' span, and 1,249 lbs for
a 10' span. For spans of 8' or less, the allowable
load is limited to 1,500 lbs. Tubes are considered
in this analysis to be braced only at the ends.
A maximum static test load of 3,400 lbs was
applied at the center of a 10' span, without
failure. Allowable loads are also limited so
that the tube's calculated deflection does not
exceed span/240. This deflection limit is often
used as a serviceability criterion for roof
framing, but permissible design deflection is
to be determined by the responsible design professional.
Adjustments of maximum test
loads were made to account for possible differences
between minimum and actual values of yield stress
and thickness. The actual maximum test load
was multiplied by the ratio of the tube's minimum-specified
yield stress to the yield stress based on a
test coupon. This partially-adjusted test value
was then multiplied by 0.93 to account for the
possibility that the tested tube had nominal
rather than minimum thickness. The ratio of
the fully-adjusted test load to the tube's allowable
load was found to exceed 2.0. Similar adjustments
were made for the strength of the End Clamp.
The ratio, of the adjusted test load to clamp
or bracket allowable, also exceeded 2.0.
The Engineer of Record is
responsible for the design adequacy of the joists
or beams that support the tube system.
|