DESIGN OF FRAMED-OPENING
SYSTEM
Summary
The framed-opening system consists
of joist clamps, framing members (channels), T-brackets
and bolts.
The
joist clamps connect the primary channels to
the
top chords of the joists. The T-brackets connect
the
secondary channels to the primary channels. Both
the joist clamps and the T-brackets have slots.
The slots,
in combination with spaced holes in the channels'
webs, permit adjustment of the framed opening's
length and
width. The position of the opening between joists
can also be adjusted by means of the slots and
holes. Analysis of the joist clamp indicates that
it can
support an allowable load of at least 1,200 lbs.
This is the
load that can be applied in addition to the framing
weight. The maximum load applied in testing was
3,940 lbs. The failure load was not reached.
Analysis and
testing considered the bolts, between channel
and clamp,
to be at the most severe location in the slots.
Analysis of the T-bracket indicates an allowable
load of substantially more than 1,200 lbs.
A test load of
2,000 lbs was applied with no failure.
The tested framing system
used hot-rolled C5 x 6.7 channels (5" deep,
weighing 6.7 pounds per foot and
made with A36 steel, which has a minimum
specified yield of 36 ksi). The maximum span
tested was slightly
more than 10'. Using the 2005 edition of
the AISC Specification, an allowable of 1,230
lbs was calculated
for
a load applied at the middle of the test
span. This assumes the channels to be unbraced
over their
entire
span.
The value of Cb was conservatively taken
to be one. A maximum test load of 4,660 lbs was
attained.
For a better comparison of the test load to the
predicted
maximum load, a reduced value of test load
was calculated. The actual test load was multiplied
by the ratio of the minimum specified yield
stress
to
the
estimated actual yield. This is a conservative
adjustment for the approximately 10' span
because this
unbraced length is close to the transition
from inelastic to elastic buckling. To account
for the
effect of
moment gradient in the test, a more accurate
value of Cb , greater than one, was used to calculate
an adjusted
(increased) value of allowable load. The
ratio
of the reduced test load to the adjusted
allowable load
was
found to exceed the desired safety factor of
2.0. |